Gas Furnace Sequence of Operation

Step by step through a call for heat on a modern induced draft furnace, and what each step proves.

Concept
Apprentice
#furnace#heating#controls#sequence

Safety

Never bypass a pressure switch, limit or rollout switch to advance the ignition sequence.

What it is

The sequence of operation is the fixed order of events a furnace follows from a call for heat to shutdown. Each step is a permission granted by a control or a safety. Knowing the sequence lets you narrow a no heat call to a single step instead of guessing.

Step 1 of 8

Thermostat Call: The thermostat closes R to W, sending a 24V call for heat.

Gas furnace sequence of operation — each step must prove before the next one is allowed

The sequence

  1. 1The thermostat closes the heat circuit and sends 24 volts to the control board.
  2. 2The board checks that the pressure switch is open, proving it is not stuck closed, then starts the inducer.
  3. 3The inducer creates negative pressure and the pressure switch closes, proving draft.
  4. 4On a hot surface ignition system the igniter warms for its programmed time. On a spark or pilot system the appropriate ignition source is energized.
  5. 5The gas valve opens and the burners light.
  6. 6The flame sensor proves flame within the trial for ignition period, typically a few seconds.
  7. 7After the blower on delay, the indoor blower starts and heat reaches the space.
  8. 8When the thermostat is satisfied the gas valve closes, the inducer runs a post purge and the blower runs an off delay before stopping.

Why it matters

Every step has a proving device. If the furnace stops at a given point, the device that should grant the next permission is the place to look. A furnace that runs the inducer and then quits is almost always a pressure switch or draft problem. A furnace that lights and drops out after a few seconds is almost always a flame sensing or grounding problem.

Stops atMost likely area
Nothing happensControl voltage, door switch, limit or rollout open, board
Inducer runs, no igniterPressure switch not closing, blocked vent, plugged trap
Igniter glows, no gasGas valve, gas supply, board output
Lights then drops outFlame sensing, grounding, gas pressure
Burner runs, no blowerBlower circuit, motor, capacitor, board
Short cycles on limitAirflow restriction or overfiring

Safety

Do not force the sequence

Jumping a pressure switch, limit or rollout switch to advance the sequence can allow combustion without proper venting. Diagnose by measuring what the control is sensing instead of bypassing it.

Local requirements

Venting, combustion air and gas piping requirements vary by jurisdiction and by the manufacturer instructions for the specific appliance.

Local Code Notice

Venting, combustion air and gas piping requirements vary by jurisdiction, adopted code edition, permits and the manufacturer instructions for the specific appliance.

Symptoms

Practice & Mastery

  • Questions2
  • Quiz1
  • Gas Furnace Sequence of Operation Troubleshooting Scenarios1

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Gas Furnace Sequence of Operation

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicIgnition Systems

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 9/29/2026.

Need a human expert? Expert Help is coming soon.