Limit and Rollout Switches
Temperature safeties that shut down heating equipment, and what each one is actually reporting.
Safety
What it is
High limit switch
A temperature sensitive switch in the heat exchanger area that opens if supply air temperature climbs too high, usually from inadequate airflow.
Rollout switch
A switch mounted near the burners that opens if flame rolls out of the burner compartment instead of drawing into the heat exchanger. Usually manual reset.
Auxiliary limit
An additional temperature safety, often on the blower compartment or near a specific hot spot.
Why it matters
A tripped rollout switch is a serious finding
A high limit that trips repeatedly is almost always an airflow problem. Each trip cycles the burner while the blower continues, and long term operation this way stresses the heat exchanger.
How it works
Both devices are normally closed and wired in series in the control circuit. Opening either one removes power from the ignition sequence and stops the burner. Most high limits reset automatically once temperature falls. Rollout switches are typically manual reset so the condition cannot repeat unnoticed.
Thermostat Call: The thermostat closes R to W, sending a 24V call for heat.
How to diagnose it
Measure temperature rise across the furnace
Above the rating plate range confirms an airflow problem behind a limit trip
Measure total external static pressure
High static identifies whether the restriction is on the return or supply side
Inspect the filter, blower wheel and evaporator coil
These are the three most common airflow restrictions
Verify gas input and manifold pressure
Overfiring raises rise and trips the limit even with adequate airflow
Inspect burners, heat exchanger and vent after any rollout trip
Rollout means combustion products took the wrong path
Test for carbon monoxide in the supply air stream and the space
Confirms whether combustion products are entering the building
Tools involved
- Thermometers for temperature rise
- Manometer for static and gas pressure
- Combustion analyzer
- Inspection camera or mirror