Sign in

Gas Furnace: No Heat

The furnace is calling for heat but the burners never light, or they light and then shut down.

Troubleshooting
Technician
#furnace#no heat#diagnostics#flame sensor

Safety

Diagnosis involves live electrical circuits and an operating gas appliance. Use proper test equipment and personal protective equipment, and never defeat a safety control.
Step 1 of 8

Thermostat Call: The thermostat closes R to W, sending a 24V call for heat.

Gas furnace sequence of operation — each step must prove before the next one is allowed

Symptom

Symptom

The thermostat is calling for heat and the furnace either does nothing, runs the inducer and stops, or lights briefly and then shuts down.

Work this fault in the order the furnace itself works. Each stage of the sequence of operation has to prove before the next one is permitted, so the stage that stops is the stage that failed.

What you observe

  • Nothing happens at all - no inducer, no board activity.
  • The inducer runs continuously but nothing else happens.
  • The ignitor glows, the burners light, and flame drops out after a few seconds.
  • The furnace runs a short cycle then shuts down on a limit.

Possible causes

  • No 24 volt control power - failed transformer, tripped door switch, or blown low voltage fuse.
  • Blocked vent, blocked condensate trap, or a failed pressure switch preventing draft proof.
  • Weak or cracked hot surface ignitor.
  • Dirty or failed flame sensor producing a low flame signal.
  • Gas supply problem - closed valve, failed gas valve, or low supply pressure.
  • Restricted airflow opening a limit switch.

What to check

Read the control board fault code before disturbing anything

The board already recorded which stage failed - reading it first saves most of the diagnostic time.

Measure 24 volts between R and C at the board during a call

No control voltage points to the transformer, fuse, or a safety in the control circuit.

Measure pressure switch closure with the inducer running

An open switch with the inducer running points to the vent, the trap, the hose, or the inducer itself - not to the switch.

Measure flame signal in microamps during the trial for ignition

A reading below the manufacturer minimum explains a flame that lights and drops out.

Measure temperature rise across the heat exchanger

A rise above the data plate range means airflow is the underlying problem, not the limit switch that tripped.

Next step

Correct the condition the failing stage revealed, then run the furnace through a full cycle and confirm every stage proves normally. Verify temperature rise is within the data plate range before leaving.

Safety note

Never bypass a safety

Pressure switches, limits, rollout switches and flame proving exist to prevent combustion hazards. Jumpering one to keep an appliance running is not a repair. If a heat exchanger failure is suspected, the appliance is taken out of service.

Local Code Notice

Gas appliance service, venting and combustion requirements vary by jurisdiction, adopted code edition and equipment. Verify local codes, permits and manufacturer instructions.

Symptoms

Step-by-step: Gas furnace: no heat

Work through the checks in order rather than guessing.

Practice & Mastery

  • Gas Furnace: No Heat Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Gas Furnace: No Heat

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicAir Conditioner Not Cooling

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 10/9/2026.

Need a human expert? Expert Help is coming soon.