Safety switches that prove draft or protect a refrigerant circuit, and how to read what an open switch is telling you.

Component
Technician
#electrical#safety#controls#furnace

Safety

Never bypass a pressure switch to make equipment run. An open safety is reporting a real condition that must be corrected.

What it is

A pressure switch opens or closes an electrical circuit based on a pressure it senses. In HVAC there are two common families: air pressure switches that prove the draft inducer is moving flue gases, and refrigerant pressure switches that protect the compressor from unsafe high or low pressure.

SwitchSensesProtects against
Draft proving switchNegative pressure created by the inducerOperating a burner with a blocked vent or failed inducer
High pressure switchDischarge side refrigerant pressureCondenser failure, blocked airflow, overcharge
Low pressure switchSuction side refrigerant pressureRunning with a severe undercharge or a frozen coil
Loss of charge switchStanding low side pressureStarting a compressor with essentially no refrigerant

Why it matters

These switches are safeties, not nuisances

A draft proving switch that will not close is reporting a real condition, most often a blocked vent, a failing inducer or a plugged condensate trap. Jumping it can allow a burner to fire without venting, which can produce carbon monoxide indoors. Never bypass it to make a unit run.

An open pressure switch is information. Treat it as the starting point of the diagnosis rather than the failed part.

How it works

A diaphragm moves against a calibrated spring. When pressure passes the setpoint the diaphragm moves the contacts. Draft switches have a setpoint printed on the body in inches of water column, along with whether they are normally open and close on a fall in pressure.

Refrigerant switches are either automatic reset, which close again once pressure returns to a safe band, or manual reset for higher risk applications.

How to diagnose it

Measure the actual pressure the switch senses with a manometer or manifold

Compare to the printed setpoint. If the pressure is not there, the switch is right and the system is wrong

Inspect the vent, inducer wheel, hoses and condensate trap on a draft switch

Blockage, a cracked hose or a full trap are the usual causes of a switch that will not close

Measure voltage across the switch during the call

Source voltage across it means it is open. Near zero means it closed

On a high pressure trip, check condenser airflow, coil cleanliness and charge

The switch is reporting a heat rejection problem

On a low pressure trip, check for an iced coil, low airflow or a leak

Adding refrigerant without finding the leak is not a repair

Tools involved

  • Manometer for draft switches
  • Digital manifold for refrigerant switches
  • Multimeter
  • Inspection mirror and light

Symptoms

Practice & Mastery

  • Pressure Switch Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Pressure Switch

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicLimit and Rollout Switches

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 10/9/2026.

Need a human expert? Expert Help is coming soon.