Hermetic Compressor

The pump at the heart of the refrigeration circuit, common types, and how to evaluate one before condemning it.

Component
Advanced
#refrigeration#compressor#electrical#diagnostics

Safety

Recover refrigerant to an approved cylinder before opening a system. Never vent refrigerant. De-energize and lock out before electrical testing.

What it is

The compressor raises the pressure of refrigerant vapor so it will condense at a temperature above the outdoor air, and it circulates refrigerant through the system. In a hermetic compressor the motor and pump share a sealed shell cooled by returning suction gas.

TypeWhere usedNotes
ReciprocatingOlder residential and light commercialPistons and valves, tolerant of a wide range of conditions
ScrollMost current residential equipmentTwo scrolls, quieter and more efficient, sensitive to reverse rotation on three phase
RotarySmall systems, ductless unitsCompact, low tolerance for liquid return
Variable speed inverterModern high efficiency systemsDriven by a board, capacity modulates with load

Why it matters

A compressor is the most expensive component in the system, and most compressor failures are caused by something else. Liquid floodback, chronic overheating from low airflow or a dirty condenser, acid from a burnout, or repeated hard starting all kill compressors. Replacing one without finding the cause usually means replacing another.

Diagnose the system, not just the part

Before condemning a compressor, verify supply voltage under load, capacitor condition, contactor contacts, airflow on both coils, refrigerant charge and metering device operation.

How it works

Step 1 of 4

Compressor: Low pressure vapor is compressed into hot, high pressure discharge gas.

Vapor compression refrigeration cycle — heat is absorbed in the evaporator and rejected at the condenser

Suction vapor enters the shell, cools the motor windings, then is compressed and discharged. Oil circulates with the refrigerant and returns through properly sized and sloped suction lines. Internal overload protection opens on excessive current or shell temperature and resets after cooling, which is why a unit may restart on its own after a trip.

How to diagnose it

Measure voltage at the compressor terminals while it attempts to start

Sag below the manufacturer minimum points to supply, wiring or contactor problems

Clamp run current and compare to rated load amps

Locked rotor current with no start means a starting or mechanical problem

Measure winding resistance common to start and common to run with power off

Open windings or a short to the shell confirm electrical failure

Compare suction and discharge pressures after a run

A compressor that cannot build a pressure difference has internal valve or scroll damage

Check the run capacitor and contactor before condemning

Both are far more common failures and present the same way

Inspect oil and check for acid if a burnout is suspected

Determines the cleanup procedure required on replacement

High voltage and high pressure

De-energize and lock out before electrical testing. Recover refrigerant to an approved recovery cylinder before opening the system, and never vent refrigerant to atmosphere. Never apply heat or open a system containing pressure.

Tools involved

  • Multimeter and megohmmeter where appropriate
  • Clamp ammeter with inrush
  • Digital manifold
  • Recovery machine and cylinder
  • Acid test kit

Symptoms

Practice & Mastery

  • Hermetic Compressor Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Hermetic Compressor

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicMetering Devices

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 9/29/2026.

Need a human expert? Expert Help is coming soon.