Fixed orifice, thermostatic expansion valve and electronic expansion valve, and how each controls the evaporator.

Component
Advanced
#refrigeration#component#charging#diagnostics

Safety

Recover refrigerant to an approved cylinder before replacing a metering device. Never vent refrigerant.
Step 1 of 4

Compressor: Low pressure vapor is compressed into hot, high pressure discharge gas.

Vapor compression refrigeration cycle — heat is absorbed in the evaporator and rejected at the condenser

What it is

The metering device creates the pressure drop between the high and low side and controls how much liquid refrigerant enters the evaporator. It is the dividing line of the refrigeration circuit.

DeviceControl methodCharging method
Fixed orifice or pistonNo control, flow follows pressure differenceSuperheat with a manufacturer charging chart
Capillary tubeNo control, length and bore set the flowSuperheat or exact weighed charge
Thermostatic expansion valveMechanical, maintains a target superheatSubcooling to the manufacturer target
Electronic expansion valveStepper motor driven by a controllerSubcooling, with controller data for verification

How it works

A thermostatic expansion valve balances three forces: bulb pressure pushing the valve open, evaporator pressure and spring pressure pushing it closed. If the suction line warms, bulb pressure rises and the valve feeds more refrigerant, holding superheat roughly constant across a range of loads.

A fixed orifice has no feedback. As load changes, superheat changes with it, which is why charging charts for these systems require both indoor wet bulb and outdoor dry bulb.

An electronic valve uses a suction pressure transducer and a temperature sensor, and a controller drives a stepper motor. It holds superheat tightly and can close fully on shutdown.

What can go wrong

ConditionSuperheatSubcoolingSuction pressure
Valve underfeeding or restrictionHighHighLow
Valve overfeeding or stuck openLowNormal to lowHigh
Lost bulb chargeVery high, valve closedHighVery low
Bulb poorly mounted or insulatedErraticNormalHunting
Plugged filter drier ahead of the valveHighHighLow, sometimes with a temperature drop at the drier

How to diagnose it

Verify airflow before touching the refrigerant circuit

Low airflow imitates almost every metering device fault

Measure superheat and subcooling together

The combination distinguishes charge problems from feed problems

Feel for a temperature drop across the filter drier

A noticeable drop indicates a restriction

Confirm the bulb is clamped tight, at the correct clock position and insulated

A loose or uninsulated bulb causes hunting and erratic superheat

Check the external equalizer line for kinks or blockage

A blocked equalizer causes a valve to underfeed

Tools involved

  • Digital manifold with temperature clamps
  • Manufacturer charging chart
  • Infrared or contact thermometer
  • Nitrogen and brazing equipment for replacement

Symptoms

Practice & Mastery

  • Questions1
  • Metering Devices Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Metering Devices

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicReversing Valve

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 9/21/2026.

Need a human expert? Expert Help is coming soon.