Flame Sensing and Rectification
How a furnace proves flame with a single rod, and how to measure and interpret the microamp signal.
Safety
What it is
A flame sensor is a single metal rod placed in the burner flame. The control board applies alternating current to the rod and the flame, being conductive and asymmetric, allows current mostly in one direction. The resulting small direct current tells the board flame is present.
Flame signal is measured in microamps, commonly 1 to 6 on residential equipmentAlways compare to the minimum value the manufacturer specifies for that board.
Why it matters
Flame sensing is the safety that prevents raw gas from flowing without combustion. It is also one of the most common causes of intermittent no heat calls, because a thin oxide layer on the rod slowly reduces the signal until the board drops out after a few seconds of burner operation.
How to measure it
- 1Turn off power and gas, then place the meter in series with the sensor wire using the microamp range.
- 2Restore power and gas and start a heat call.
- 3Read the signal once the burners are fully lit and stable.
- 4Compare to the manufacturer minimum. A signal near the minimum will fail as the rod ages.
- 5If low, clean the rod gently with a non abrasive pad, never sandpaper, and recheck.
- 6If cleaning does not restore the signal, check the ground path, burner condition, gas pressure and flame quality.
Signal drops steadily during the run
Often a marginal ground or a sensor positioned at the edge of the flame
Signal is strong but the board still drops out
Suspect the board or the sensor wire insulation grounding out
Yellow or lifting flame
A combustion problem, not a sensor problem. Check gas pressure, burners and combustion air
Signal restored by cleaning but fails again within months
Look for combustion byproducts, poor burner condition or an air supply contamination issue
Safety
Never bypass flame proving
Tools involved
- Meter with a microamp direct current range
- Alligator jumper leads
- Non abrasive cleaning pad
- Combustion analyzer to confirm flame quality
Symptoms