Start Capacitor and Hard Start Kit

What a start capacitor does during the first moments of a motor start, and when a hard start kit is appropriate.

Component
Technician
#electrical#capacitor#compressor#motors

Safety

Capacitors store a dangerous charge. De-energize, lock out and discharge with a resistor before handling.
HERM
C (common)
FAN
Dual run capacitor terminals — HERM serves the compressor, FAN serves the condenser fan, C is common

What it is

A start capacitor is a high capacitance, short duty device that gives a single phase motor extra starting torque. Unlike a run capacitor it stays in the circuit only for the first fraction of a second, then a potential relay or a current sensing device removes it.

Hard start kit

A start capacitor paired with a switching device, added to a compressor that struggles to start. Sold as a matched potential relay and capacitor, or as a self contained solid state module.

Why it matters

A compressor that cannot break away draws locked rotor current until the internal overload opens. Repeated attempts heat the windings and shorten the life of the compressor. A properly selected start assist reduces the time spent at locked rotor current.

A hard start kit is not a cure for a mechanical problem

If a compressor needs start assist, find out why. Low voltage, a weak run capacitor, equalization problems from a failed metering device, or a compressor nearing the end of its life all present as hard starting. Adding a kit without diagnosing the cause only hides the condition.

How it works

  1. 1On a call for cooling the contactor closes and the compressor attempts to start.
  2. 2The start capacitor is in series with the start winding, shifting the phase further and creating more starting torque.
  3. 3As the motor comes up to speed the start winding generates a back electromotive force.
  4. 4The potential relay senses that voltage and opens its contacts, removing the start capacitor.
  5. 5The run capacitor remains in the circuit for normal operation.

Start capacitors are rated in a microfarad range rather than a single value, along with a voltage rating. Most include a bleed resistor across the terminals to discharge the capacitor between starts.

How to diagnose it

Listen and clamp the compressor on a start attempt

Current at locked rotor for more than a moment, with a hum and no start, points to a starting problem

Verify supply voltage while the compressor attempts to start

Significant sag indicates a supply or connection problem rather than a capacitor

Test the run capacitor first

A weak run capacitor is the most common cause of hard starting

Measure the start capacitor with a capacitance meter after discharging

A reading outside the printed range, or an open bleed resistor, means replace

Check the potential relay coil and contacts

Welded contacts leave the start capacitor in circuit and destroy it quickly

Discharge before touching

Capacitors hold a dangerous charge after power is removed. De-energize, lock out and discharge through an appropriate resistor before handling. Never short terminals with a screwdriver.

Tools involved

  • Multimeter with capacitance function
  • Clamp ammeter with inrush capability
  • Insulated tools and eye protection
  • Discharge resistor

Symptoms

Practice & Mastery

  • Start Capacitor and Hard Start Kit Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Start Capacitor and Hard Start Kit

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicPSC Motor

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 9/30/2026.

Need a human expert? Expert Help is coming soon.