A low current coil switching a higher current load, and the relay types you meet in HVAC controls.

Component
Apprentice
#electrical#controls#relay#diagnostics

Safety

De-energize and lock out before removing or testing a relay out of circuit.

What it is

A relay uses a small electromagnet to move a set of contacts. A control circuit energizes the coil, the contacts change position, and a separate circuit is switched. This lets a 24 volt thermostat circuit control line voltage loads safely.

TypeCoilTypical use
General purpose relay24 volts alternating currentSwitching a blower, a damper motor or an accessory
Fan relay24 voltsEnergizing the indoor blower on a fan call
Potential relaySenses start winding voltageRemoving a start capacitor from the circuit
Current relaySenses run winding currentStart assist on small hermetic compressors
Solid state relayLow voltage signalStaging electric heat or controlling without moving contacts

Why it matters

Relays are the point where the control circuit meets the load. When something does not run, the relay tells you which side of the problem you are on. Coil energized and contacts not passing power means the relay failed. Coil not energized means the fault is upstream in the control circuit.

Contact arrangements

  • Normally open contacts are open with the coil de-energized and close when energized.
  • Normally closed contacts are closed at rest and open when energized.
  • A single pole double throw relay has a common terminal that moves between a normally open and a normally closed terminal.
  • Contacts are rated for a specific current and load type. Using a relay below its rating leads to welding and pitting.

How to diagnose it

Measure voltage across the coil during a call

Rated voltage present means the control side is doing its job

Listen and feel for the click when the coil energizes

No movement with rated coil voltage means an open or seized coil

Measure voltage across the closed contacts

Near zero is healthy. Significant voltage across closed contacts means resistance and burning

Measure coil resistance with power off

Open reads infinite, shorted reads very low and will blow the transformer fuse

Check whether contacts stay closed with the coil de-energized

Welded contacts leave the load running continuously

Tools involved

  • Multimeter
  • Wiring diagram
  • Clamp ammeter to confirm load current

Symptoms

Practice & Mastery

  • Relay Troubleshooting Scenarios2

Practice is part of HVAC Pro — $5/month or $50/year.

AI Tutor

Ask AI about Relay

The AI Tutor knows the topic you are reading and teaches from the Welcome to HVAC knowledge base. Included with HVAC Pro — $5/month or $50/year.

Next topicRun Capacitor

Educational reference only. Verify procedures against manufacturer instructions and local code. Last updated 9/29/2026.

Need a human expert? Expert Help is coming soon.