Why an outdoor coil frosts in heating, how the control decides to defrost, and what normal defrost looks like.

Concept
Technician
#heat pump#heating#defrost#controls

What it is

In heating mode the outdoor coil is the evaporator and operates below outdoor air temperature. When that coil surface falls below freezing and the air carries moisture, frost forms. Defrost temporarily reverses the system to melt it off.

Step 1 of 6

Compressor: The compressor raises refrigerant pressure and temperature, so hot discharge gas leaves it in either mode.

Heat pump refrigerant flow — heating — the reversing valve decides which coil evaporates and which condenses

How defrost runs

  1. 1The defrost control decides defrost is needed, using a coil temperature sensor combined with either accumulated run time or a demand calculation.
  2. 2The reversing valve shifts to the cooling position so hot discharge gas flows to the outdoor coil.
  3. 3The outdoor fan stops so the coil warms quickly.
  4. 4Auxiliary electric heat is usually energized so the indoor air does not blow cold.
  5. 5Defrost ends on coil temperature, or on a maximum time limit if the sensor does not terminate it.
  6. 6The system returns to heating and the outdoor fan restarts.

Steam rising from the outdoor unit during defrost is normal. A brief whoosh as the reversing valve shifts is also normal.

What can go wrong

SymptomLikely cause
Coil stays iced, unit keeps runningDefrost never initiating: failed sensor, failed board, or low charge keeping coil temperature odd
Defrost runs constantlySensor out of calibration, board fault, or restricted outdoor airflow
Ice only at the bottom of the coilDrainage problem, defrost water refreezing, or unit set too low to the ground
Cold air indoors during defrostAuxiliary heat not energizing during defrost
Unit never reaches setpoint in cold weatherBelow balance point, or a charge or airflow problem

How to diagnose it

Force a defrost using the manufacturer procedure

Confirms whether the valve shifts, the fan stops and auxiliary heat energizes

Measure the defrost sensor resistance against the manufacturer curve at a known temperature

A drifted sensor is a common cause of poor defrost timing

Verify charge by the manufacturer method for heating mode

Low charge lowers coil temperature and worsens frosting

Check outdoor coil cleanliness and clearance

Restricted airflow keeps the coil colder than it should be

Confirm the unit sits high enough above grade with free drainage

Meltwater that cannot drain refreezes into a block of ice

Tools involved

  • Digital manifold with temperature clamps
  • Multimeter
  • Manufacturer defrost sequence and sensor resistance chart

Symptoms

Practice & Mastery

  • Questions2
  • Quiz1
  • Heat Pump Defrost Cycle Troubleshooting Scenarios2
  • Heat Pump Defrost Cycle Equipment Scenarios1

Practice is part of HVAC Pro — $5/month or $50/year.