Electric Backup Heat Strip Calculator
Auxiliary heat strips are resistance heaters; their current is power divided by voltage.
HVAC Pro calculator — inputs, formula and example are open to everyone.
Result
Results for this calculator are part of HVAC Pro
You can see the inputs, formula and worked example. Unlock results for every Pro calculator.
Unlock with HVAC ProAlready a member? Sign in
Formula
- I = (kW × 1000) ÷ V
- BTU/h = kW × 3,412
Example calculation
10 kW at 240 V → 41.7 A, 34,121 BTU/h.
Practical HVAC use
Check strip operation with an amp clamp and confirm staging.
Common mistakes
- Forgetting that 240 V-rated strips produce about 75% of rated output at 208 V.