Indoor Blower Will Not Run
Tracing a dead blower across PSC and ECM equipment without guessing at parts.
Safety
Symptom
Symptom
No air from the registers on a fan call, a heat call, or a cooling call.
Symptom
Or the blower runs in one mode but not another.
Possible causes
- Door switch held open by a panel that is not fully seated.
- No line voltage to the air handler or furnace.
- Open control circuit, blown low voltage fuse or failed transformer.
- Failed fan relay, blower relay on the board, or an open sequencer contact on electric heat equipment.
- Failed run capacitor on a PSC blower.
- Failed ECM control module or missing control signal.
- Seized bearings or a blower wheel jammed by debris.
- Open thermal overload in the motor after an overheat event.
What to check, in order
Door switch and panel fit
A very common no blower call. Hold the switch closed only as a momentary test, never defeat it permanently
Line voltage at the equipment and 24 volts at the board
Establishes which side of the system has lost power
Low voltage fuse on the board
A blown fuse points to a short in the thermostat or accessory wiring
Control signal at the blower terminal during the call
Signal present with no motor response moves the fault to the motor or module
Run capacitor on a PSC motor after discharging
Out of tolerance prevents the motor from starting and often produces a hum
Whether the wheel turns freely with power off and locked out
Drag or debris indicates bearings or a mechanical obstruction
Motor winding resistance and amp draw on a start attempt
Open windings or locked rotor current confirm motor failure
ECM module line voltage, polarity and commanded signal
Separates a failed module from failed windings
The door switch is a safety device
Next step
If the motor overheated, find the reason. A clogged filter, a dirty blower wheel or excessive static pressure all overwork a blower. After the repair, measure total external static pressure and either temperature rise or temperature split to confirm the airflow is where it should be.
Tools involved
- Multimeter
- Capacitance meter
- Clamp ammeter
- Manometer with static pressure tips