Voltage Drop Calculator (Copper & Aluminum)
Long runs to condensers and rooftop units can drop enough voltage to affect motor performance.
HVAC Pro calculator — inputs, formula and example are open to everyone.
Result
Results for this calculator are part of HVAC Pro
You can see the inputs, formula and worked example. Unlock results for every Pro calculator.
Unlock with HVAC ProAlready a member? Sign in
Conductor areas from NEC Chapter 9 Table 8; approximate K at ~75 °C. Verify with CEC/NEC requirements.
Formula
- Single-phase: VD = 2 × K × I × L ÷ CM
- Three-phase: VD = 1.732 × K × I × L ÷ CM
Variables
- K
- — 12.9 (copper) or 21.2 (aluminum) Ω·cmil/ft
- L
- — One-way length (ft)
- CM
- — Conductor area in circular mils
Example calculation
10 AWG copper, 24 A, 100 ft one-way, 240 V single-phase → 5.97 V (2.5%).
Practical HVAC use
Check condenser and long branch circuits before installation.
Common mistakes
- Entering round-trip length (the formula already doubles it).
- Ignoring voltage drop at motor starting.
Related calculators
Wire Resistance
ProCalculate conductor resistance for copper or aluminum wire by AWG size and length.
Three-Phase Amps
ProCalculate three-phase line current from kW, voltage and power factor.
Motor Amps from HP
ProEstimate motor full-load current from horsepower, voltage, efficiency and power factor for single or three-phase motors.
Educational tool. Results are estimates from the stated formulas; always confirm with manufacturer data and the code adopted in your jurisdiction. All calculators