Voltage Drop Calculator (Copper & Aluminum)

Long runs to condensers and rooftop units can drop enough voltage to affect motor performance.

HVAC Pro calculator — inputs, formula and example are open to everyone.

Result

Results for this calculator are part of HVAC Pro

You can see the inputs, formula and worked example. Unlock results for every Pro calculator.

Unlock with HVAC Pro

Already a member? Sign in

Conductor areas from NEC Chapter 9 Table 8; approximate K at ~75 °C. Verify with CEC/NEC requirements.

Formula

  • Single-phase: VD = 2 × K × I × L ÷ CM
  • Three-phase: VD = 1.732 × K × I × L ÷ CM

Variables

K
— 12.9 (copper) or 21.2 (aluminum) Ω·cmil/ft
L
— One-way length (ft)
CM
— Conductor area in circular mils

Example calculation

10 AWG copper, 24 A, 100 ft one-way, 240 V single-phase → 5.97 V (2.5%).

Practical HVAC use

Check condenser and long branch circuits before installation.

Common mistakes

  • Entering round-trip length (the formula already doubles it).
  • Ignoring voltage drop at motor starting.