Sensible Heat Calculator (1.08 × CFM × ΔT)
Sensible heat changes air temperature without changing its moisture. It is the most-used airflow/capacity relationship in the field.
HVAC Pro calculator — inputs, formula and example are open to everyone.
Result
Results for this calculator are part of HVAC Pro
You can see the inputs, formula and worked example. Unlock results for every Pro calculator.
Unlock with HVAC ProAlready a member? Sign in
Formula
- Q (BTU/h) = 1.08 × CFM × ΔT (°F)
Variables
- 1.08
- — 0.075 lb/ft³ × 0.24 BTU/lb·°F × 60 min/h (standard air)
- ΔT
- — Supply–return temperature difference
Example calculation
1,200 CFM × 20 °F ΔT × 1.08 = 25,920 BTU/h (7.6 kW).
Practical HVAC use
Estimate delivered heating or sensible cooling capacity, or back-calculate airflow from capacity and ΔT.
Common mistakes
- Using the formula at high altitude without a density correction.
- Using total cooling capacity — only the sensible portion applies.