Refrigeration Capacity from Enthalpy Difference

Refrigeration effect equals mass flow times the enthalpy gained across the evaporator.

HVAC Pro calculator — inputs, formula and example are open to everyone.

kg/s
kJ/kg
kJ/kg

Result

Results for this calculator are part of HVAC Pro

You can see the inputs, formula and worked example. Unlock results for every Pro calculator.

Unlock with HVAC Pro

Already a member? Sign in

Enthalpy values must come from verified refrigerant property tables for your refrigerant.

Formula

  • Q = ṁ × (h₂ − h₁)

Variables

ṁ
— Refrigerant mass flow (kg/s)
h₁
— Enthalpy entering evaporator (kJ/kg)
h₂
— Enthalpy leaving evaporator (kJ/kg)

Example calculation

0.05 kg/s × (405 − 250) kJ/kg = 7.75 kW ≈ 2.2 tons.

Practical HVAC use

Teaching the cycle on a P-h diagram and checking published performance data.

Common mistakes

  • Reading enthalpy from a chart for a different refrigerant.