Refrigeration Capacity from Enthalpy Difference
Refrigeration effect equals mass flow times the enthalpy gained across the evaporator.
HVAC Pro calculator — inputs, formula and example are open to everyone.
Result
Results for this calculator are part of HVAC Pro
You can see the inputs, formula and worked example. Unlock results for every Pro calculator.
Unlock with HVAC ProAlready a member? Sign in
Enthalpy values must come from verified refrigerant property tables for your refrigerant.
Formula
- Q = ṁ × (h₂ − h₁)
Variables
- ṁ
- — Refrigerant mass flow (kg/s)
- h₁
- — Enthalpy entering evaporator (kJ/kg)
- h₂
- — Enthalpy leaving evaporator (kJ/kg)
Example calculation
0.05 kg/s × (405 − 250) kJ/kg = 7.75 kW ≈ 2.2 tons.
Practical HVAC use
Teaching the cycle on a P-h diagram and checking published performance data.
Common mistakes
- Reading enthalpy from a chart for a different refrigerant.